Descrizione

Function Emergency stop module with delay up to 300s
Also suited as safety gate monitor +
Cat. / PL according to EN ISO 13849-1 4/e
SIL CL according to IEC/EN 62061 3
1- / 2-channel 1, 2
Output contacts max. 2 s, 1 sv
Thermal current Ith max. 8 A
Cross fault detection +
Nominal voltage DC +
Connection PS/PC
Width 22,5 mm
Type LG 5928
According to- Performance Level (PL) e and category 4 to EN ISO 13849-1: 2008- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511 Output: 2 NO instantaneous contacts and 1 release delay contact 1- or 2-channel connection Line fault detection at the ON pushbuttons at connection onterminals S33-S34 Manual restart with button on S33-S34 or automatic restart withbridge between S13-S34 With or without cross fault monitoring in the E-stop loop Indication for released time circuit LED indication for supply, channel 1/2 and release delayed contacts Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated),DIN 46 228-1/-2/-3/-4 or 2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3 As option with pluggable terminal blocks for easy exchange of devices- with screw terminals- or with cage clamp terminals Width 22.5 mm''